4.17 KEW6305
Setting 15” Target demand
For details about demand target value, please refer to “Section 8”: Demand measurement. Target
value can be selected between 0.1W and 999.9GW.
Value Unit
Demand target value
0.1 - 999.9
(can be set by 0.1)
W / kW / MW / GW
VA / k VA / M VA / G VA
Default value (or after
system reset)
100.0kW
1 Use the Cursor key on the selection screen, and select “Setting 15”.
2 Press the ENTER key to get the instrument into setting change mode.
3 Present setting (or default value: 100.0kW) blinks. Change the value and unit with the Cursor key.
4 Press the ENTER key after making necessary change.
Function of Cursor keys:
To select the digit or unit parameter subject to change.
To change the value of selected digit and unit parameter.
Either “W” or “VA” can be set as a unit.
The instrument can display and record the demand values of active and apparent power by switching
above unit.
NOTE:
* When the target value is set to 0.0, it is forcefully changed into 100.0.