5.5 KEW6305
5.4 Wiring check
This instrument has Wiring check function to check the connections in order to prevent incorrect
connections.
5.4.1 Check procedure
1 Rotate the Function switch to “WIRING CHECK” position. (Ensure that necessary Voltage test leads/
Clamp sensors are connected to the instrument/ circuit under test.)
2 Press the ENTER Key. (Check will start.)
3 Check result will be displayed about 5 sec. later.
_ Everything is OK._ _ Error is found._
Top:
Frequency f
Middle:
Voltage
Bottom:
Current A